logo
Casa > prodotti >
Indicatore di guasti del cavo
>
High Voltage Cable Tester with High-voltage Pulse and Three-level Adjustment for Precise Detection

High Voltage Cable Tester with High-voltage Pulse and Three-level Adjustment for Precise Detection

Dettagli del prodotto:
Luogo di origine: Xi'an Shaanxi Cina
Marca: XZH TEST
Certificazione: ISO CE
Numero di modello: XHHV535-4TS
Informazione dettagliata
Luogo di origine:
Xi'an Shaanxi Cina
Marca:
XZH TEST
Certificazione:
ISO CE
Numero di modello:
XHHV535-4TS
Evidenziare:

High Light

Evidenziare:

High-voltage pulse Cable Fault Locator

,

Three-level adjustment Cable Fault Detector

,

Precise detection High Voltage Cable Tester

Trading Information
Quantità di ordine minimo:
1 set
Imballaggi particolari:
imballaggio in legno
Tempi di consegna:
5-8 GIORNI LAVORATIVI
Termini di pagamento:
T/T
Capacità di alimentazione:
3000 unità/anno
Descrizione di prodotto

XHHV535-4TS


It is primarily used for impulse discharge and withstand voltage testing during fault testing of low and high voltage cables.


Product Features:


High-voltage pulse output is uniform and controllable;
Features dual 2.5-level pointer meters for current and voltage display, providing a clear and intuitive view of the impulse discharge process;
High-voltage side voltage measurement is real-time and accurate;
Equipped with zero-start protection function, ensuring safety and reliability;
Features three voltage range and capacitance capacity switching functions;
Unique high-voltage measurement design automatically discharges the internal capacitor energy when the device is stopped;
Discharge time can be selected in either timed or manual mode;
Includes DC withstand voltage function;
Internally installed high-precision test cable fault waveform sampling module;
Humanized design with a trolley for easy movement;


Technical Parameters
Impulse High Voltage: 0-32kV, 0-16kV, 0-8kV (three adjustable ranges)
High Voltage Side Current: 0-60mA
High Voltage Accuracy: Class 2.5
Built-in Capacitance: 4μF/32kV, 16μF/16kV, 64μF/8kV (three adjustable ranges)
Discharge Energy: 2048J (for all ranges)
Output Voltage Polarity: Negative polarity
Impulse Time: Automatic impulse approximately 7 seconds, manual impulse with arbitrary time control
Overcurrent Protection: 9A (greater than 5S) on the low voltage side
Over-temperature Protection: 105℃
Maximum Power: 2000W
Operating Power Supply: AC 220V±10% 50Hz±2Hz
Ambient Temperature: -25~+65℃